Pressure Transmitter for CDU Liquid Cooling: Six Field Conditions and the Choice at 1.6 MPa

From: Issued date 2026.11.26 Back

A coolant distribution unit runs the same loop, at the same pressure, for years. The pump starts and stops a few hundred times a week, the supply temperature steps when the IT load changes, and nothing in the cabinet ever gets switched off for maintenance. The pressure transmitter sitting on that loop is asked to survive all of it and still read within its accuracy class.

Most selection conversations about CDU instrumentation start with range and accuracy, which are the two numbers the datasheet makes easiest to compare. They are also the two numbers that rarely decide whether the instrument is still working in year three. What decides it is the pressure boundary, the temperature band the electronics were actually compensated over, and the surge the pump puts through the line every time it starts.

Schematic of a coolant distribution unit: primary loop, heat exchanger, pump, secondary loop to the racks, and the three points where a pressure transmitter is normally fitted

What a CDU cooling loop asks of a pressure transmitter

Six conditions separate a cooling loop from a general industrial application, and each one maps to a different part of the specification. Reading them in this order is more useful than reading a datasheet top to bottom.

ConditionWhat it does to the instrumentWhere it shows up in the specification
Continuous circulationThe wetted parts see the same coolant, with its inhibitor package, for the life of the unitWetted material and seal material, not accuracy
Repeated pressure cyclingEvery pump start and valve movement is a pressure step on the diaphragmCycle life of the sensing element, and the surge margin
Pump start and stop surgeShort pressure spikes well above the steady reading, in both directionsOverload and burst rating; whether a snubber is needed
Supply temperature stepsThe housing and the sensing element sit at different temperatures while the step is runningThe band the unit was compensated over, and the temperature effect figure
Continuous vibrationConnector and cable entry take the load; a loose joint becomes an intermittent signalConnector type, strain relief, mounting
Permanent electrical noiseVariable-frequency drives and switch-mode supplies sit in the same cabinetOutput type, shielding, wiring practice

None of these is exotic. The point is that five of the six are decided by the housing, the seal and the wiring rather than by the accuracy class, which is why a unit that looks better on paper can be the worse choice for a CDU.

The pressure boundary is the part that fails quietly

Coolant leaks in a data hall are expensive in a way that a wrong reading is not. A drifting transmitter produces a bad number and an alarm; a seeping joint produces damaged hardware in the next rack. So the question worth asking about any CDU transmitter is not how it is calibrated but what, exactly, is holding the coolant inside.

There are two common answers. One is a sensing element sealed into its housing with an elastomer ring, with the ring doing the sealing and the thread doing the mechanical work. The other is a welded body, where the pressure boundary is metal fused to metal and no elastomer sits in the path at all.

Cross-section comparison of an elastomer-sealed sensing element and a welded element: in the first the O-ring carries the pressure boundary, in the second the weld does

The difference is not about initial tightness. Both seal on day one. It is about what happens over a few hundred thousand pressure and temperature cycles: an elastomer takes a permanent set, loses contact stress and starts to weep, while a welded boundary removes that mechanism rather than acquiring a different one for free. A weld has its own dependencies — joint design, weld quality, residual stress, and resistance to pressure and thermal cycling — and, in a coolant carrying chlorides, resistance to stress-corrosion cracking. What a welded boundary does not have is a rubber part that relaxes with age.

PCM390 is built the second way. The sensing element is welded into its housing with a continuous laser weld, the same construction used across the 320 and 308 builds, and there is no separate O-ring groove sealing the element into the body. Wetted parts are 316L and the upper housing is 304; the element sits on a glass-sintered base, which is where much of its dielectric strength comes from.

The trade-off belongs in the same breath, because it is the honest half of the comparison. A welded assembly is more reliable and lasts longer in a hard environment, and it is not a repairable assembly: if the element fails, the housing and its thread go with it. An element sealed in by a ring can be replaced, and it carries a part that relaxes with age. Which of those two risks matters more depends on whether the loop is serviced or sealed for life.

Assembly area at the WTsensor plant in Nanjing, where pressure sensing elements are assembled, welded into their housings and calibrated

What stays a buying question, whatever the construction, is the process joint: thread, mating surface and washer decide it, and it is a separate item on most thread codes. That belongs in the order rather than in the hope.

That distinction also decides what to check about the coolant. Compatibility depends on the glycol concentration, the inhibitor formulation, the chloride level, the operating temperature and the exposure pattern, and those variables do not act in the same way. Chloride is the one that matters most to a 300-series stainless, because pitting and stress-corrosion cracking begin at welds and crevices; the inhibitor package matters for different reasons, which are pH control and the protection of the other metals in the loop. 316L is widely used in industrial cooling systems, and that is not the same statement as 316L suiting every water-glycol formulation. The material question is not "is it 316L" but "has this grade been checked against this concentrate".

Where the gauge build stops: 35 kPa to 1.6 MPa, and one rating offered twice

A CDU enquiry usually states a range and a pressure type in one line, and that line is where the errors concentrate, because the range table does not offer every combination. On PCM390, gauge (G) covers 35 kPa to 1.6 MPa. Sealed gauge (S) covers 1.6 to 25 MPa. Absolute (A) exists at two points only, 100 kPa and 250 kPa.

Range codeTypeRangeOverloadBurst
35kG0–35 kPa300 % FS600 % FS
70kG0–70 kPa300 % FS600 % FS
100kG, A0–100 kPa200 % FS500 % FS
160kG0–160 kPa200 % FS500 % FS
250kG, A0–250 kPa200 % FS500 % FS
400kG0–400 kPa200 % FS500 % FS
600kG0–600 kPa200 % FS500 % FS
1MG0–1 MPa200 % FS500 % FS
1.6MG, S0–1.6 MPa200 % FS500 % FS
2.5MS0–2.5 MPa200 % FS500 % FS
4MS0–4 MPa200 % FS400 % FS
6MS0–6 MPa200 % FS300 % FS
10MS0–10 MPa200 % FS300 % FS
16MS0–16 MPa150 % FS200 % FS
25MS0–25 MPa150 % FS200 % FS

PCM390 range codes by pressure type: gauge runs from 35 kPa to 1.6 MPa, sealed gauge from 1.6 to 25 MPa, absolute only at 100 kPa and 250 kPa, with the 1.6 MPa rating offered as both G and S

Two things in that table are worth pausing on. The first is the 1.6 MPa rating: it appears in the table with both G and S against it, and no other row does. That makes it the one place in the range where the pressure type is a real decision rather than a consequence of the range: a gauge unit carries a vent to atmosphere, so the reading includes barometric variation and the vent has to be able to breathe; a sealed-gauge unit closes the reference side into a chamber, so the reading excludes it and there is no vent path for condensation to follow. On a loop that runs cold or gets washed down, that difference matters more than the class.

The second is the surge margin, which is not constant across the family. Overload sits at 300 % of range at the two smallest ratings, 200 % through the middle, and 150 % at 16 and 25 MPa; burst falls from 600 % at the bottom to 200 % at the top. A loop running near the top of its range therefore has less headroom than the same loop running a range higher down the table, which is one reason to size on the shut-off head rather than on the working pressure.

Applied to a cooling loop: a secondary loop working at 1.2 MPa, with a pump that shuts off at 1.8 MPa, needs a range above the shut-off head, so it is a 2.5M part, and 2.5M is sealed gauge only. A loop working at 1.0 MPa and shutting off at 1.4 MPa can sit on the 1.6M rating — and there the G-or-S choice has to be made deliberately rather than by default.

Compensation is a band, not a number

The datasheet quotes two figures a few lines apart and they are easy to read as one: accuracy ±0.5 % FS typical and ±1 % FS maximum, and temperature drift ≤±1.5 % FS over −20 to 85 °C. A reader who assumes 0.5 % holds everywhere will be disappointed at the cold end of a plant room; a reader who sees 1.5 % and concludes the unit is a 1.5 % instrument will over-specify and pay for accuracy the loop does not need.

Three different quantities are in play. Reference accuracy is what the unit does at the reference temperature, and that is the 0.5 % typical and 1 % maximum pair. Temperature effect is the additional error introduced as the unit moves away from that temperature across the stated band. Total error in service is the two combined, with long-term drift on top.

How far a unit actually moves depends on how those two figures are defined: whether the temperature term is an additional error, whether it is a worst case at the band edge or a typical value, and whether the two are meant to combine arithmetically or statistically. None of that is standardised across the industry, which is why adding the numbers and calling the result the instrument's accuracy is a calculation the datasheet does not support.

What can be said without qualification is narrower and more useful: a unit held near reference conditions spends its life close to its reference accuracy, while one sitting at the band edge carries the temperature term on top of it. Where an application needs a number rather than a range, ask for the total error at the temperatures the loop actually sees.

One further detail that catches people out: the compensation band is −20 to 85 °C, while the ambient limit for the instrument is −20 to 80 °C. The unit is compensated slightly beyond the range it is rated to sit in, which is the right way round, but it means a cabinet that runs hot is limited by the ambient rating rather than by the compensation.

Pressure sensing units mounted in racks inside a temperature chamber, the step in which each unit is measured across its compensated band

The compensation itself is a per-unit process: each transmitter is run through a temperature chamber, measured at points across the band, and the correction coefficients are written into its electronics. That is work with a real cost, which is why a compensated unit has a longer lead time than an uncorrected one, and why a datasheet quoting a wide operating range next to a narrow compensation band is making two different promises.

Where PCM390 fits a CDU, and where it does not

The transmitter is a general-purpose industrial build that happens to have the right structure for a cooling loop, rather than a unit designed around one customer's cabinet. That is worth stating plainly, because it decides which parts of a CDU specification it answers.

It fits the secondary loop of a liquid-cooling skid: 1.6 MPa and below as a gauge unit, above that as sealed gauge, which covers the band where most CDUs sit. The 22 mm hex and the 50 to 90 g body matter in a cabinet where the manifold is already crowded. Three outputs cover the usual control platforms — 4–20 mA and 0–10 V two- or three-wire on 12–30 V, and a 0.5–4.5 V ratiometric output on 5 V — and four connector families (cable outlet, M12, mini Hirschmann, Packard) cover most harness conventions. The ordering table itself sits on the PCM390 product page. The pin count has to be matched to the output, because the ratiometric version carries supply and signal on separate pins.

PCM390 pressure transmitter for CDU liquid cooling, showing the process connections and the cable, M12, mini-Hirschmann and Packard electrical interfaces

It does not fit ranges under the 35 kPa entry point, media outside −30 to 105 °C, an installation whose ambient runs outside −20 to 80 °C, or a loop that needs better than the combined error above at the band edges. Several of those have a different answer inside the same catalogue: a higher-range rating where pressure alone is the issue, and a glass micro-fused element where the medium attacks an oil-filled boundary.

PCM390 is already in service in liquid-cooling projects. If your loop sits inside the envelope above, the rest of this article is about the order; if it does not, the honest answer is that this is the wrong family, and the enquiry should say so.

The ordering fields that decide whether it survives

Five fields change the outcome more than the accuracy class does, and most of them are left blank until the supplier asks.

Pressure type, then range. The two are not independent. Gauge covers 35 kPa to 1.6 MPa, sealed gauge 1.6 to 25 MPa, absolute 100 kPa and 250 kPa. The 1.6 MPa rating accepts either G or S, so at that one point the choice is yours to make rather than the table's.

Thread and seal. Five connection codes are printed — G1/4, NPT1/4-18, NPT1/8, and 7/16-20 UNF in male and female — with a recommended torque of 15 to 25 N·m that depends on gasket material, mating material, thread lubrication and pressure rather than on the thread alone. The seal is a separate item on most codes, so what ships with the code you order has to be confirmed rather than assumed. On a coolant loop that is the difference between a specified joint and one improvised at commissioning.

Surge protection. The manual is explicit that cavitation, liquid hammer and pressure peaks arise wherever flow rate changes — a valve closing quickly, a pump starting or stopping — and that they occur at the inlet and outlet even at relatively low operating pressures. So the question is not whether the loop passes some pressure threshold, but whether a peak can exceed the dynamic pressure the element is rated for. The M4 damper is the accessory for it, and it is not offered on thread codes C12, C34 and C36.

Electrical interface. Connector and cable entry fix the practical IP rating more than the housing does. A plug that is not fully seated, or a gland tightened onto the jacket rather than the shield, undoes an IP65 housing in one commissioning visit.

Output and supply. Three outputs are offered: 4–20 mA and 0–10 V on 12–30 V, and the 0.5–4.5 V ratiometric version on 5 V. The last one needs a precise 5 V rail; feeding it 24 V damages the signal and eventually the unit. Where the platform allows a choice, 4–20 mA is the version that survives a long cable run next to a variable-frequency drive.

What to put in the enquiry

A CDU enquiry that arrives with these six items gets a correct quotation the first time. Without them, the supplier picks a default, and the default may not be the one that fits.

  • The loop: primary or secondary, working pressure and the pump's shut-off head, and whether the tapping sits near a valve that closes quickly.

  • Pressure type: gauge, absolute or sealed gauge, and whether the cabinet is sealed or ventilated.

  • Coolant: the glycol concentration and, if available, the inhibitor chemistry — the chloride and amine content decides the wetted material question.

  • Temperature: the supply and return temperatures, plus the ambient the transmitter body will sit in.

  • The interface: thread, seal type, connector family, output and supply voltage.

  • The record you need: whether a per-unit calibration certificate and the compensated-band data are part of the deliverable.

Need a transmitter matched to a cooling loop?

Send the loop conditions, the pressure type, the coolant and the electrical interface. With those, the answer is specific: which range, which seal, whether a snubber is warranted, and whether the compensated band covers the installation.

Requirements can be sent through the online message form or by email to dr@wtsensor.com. The same address is in the contact block of every datasheet and can be used to request a calibration record for a specific configuration as well as a quotation.

Where to go next

About WTsensor

Nanjing Wotian Technology has been building pressure instruments since 2005. The sensing element, the assembly, the temperature compensation and the calibration happen in one plant rather than across a supply chain, which is what lets a coolant-loop question be answered at the level of the joint rather than the catalogue.

WTsensor factory in Nanjing: 20 years of production experience, 4.5 million pressure sensors a year, 70,000 square metres of production area

The range covers pressure, differential, level and temperature, on diffused-silicon and glass micro-fused sensing technologies, in housings from a bare core to a flameproof instrument. Liquid cooling, CDU and energy storage sit inside that range rather than beside it, and the selection logic in this article is the same one applied to any loop with a coolant in it.

WTsensor product range: pressure sensors and transmitters for water, oil, air and gas

Questions that come up in every enquiry

Is a standard industrial transmitter good enough for a CDU? Often yes, provided the pressure boundary suits a loop that runs continuously and the compensated band covers the installation. The failure mode to avoid is not inaccuracy but a seal that ages, which is a question about construction rather than about class.

Why does the compensation band matter more than the operating range? The operating range says the unit will function; the compensated band says the unit was corrected for its error over that span. Outside the compensation band the output is still valid, but the temperature effect is no longer the figure on the datasheet.

Gauge or absolute for a CDU loop? Gauge is the usual choice where the cabinet is vented and the reading is compared with a local gauge. Absolute or sealed gauge avoids a vent path that can block or draw in condensation, and it removes the barometric term from the reading.

At what pressure does a loop need a snubber? No single pressure answers it. Cavitation, water hammer and pressure peaks appear wherever flow velocity changes, and they can arise at fairly low operating pressures. What to check is the peak that a valve closure or a pump stop can put on the port, and whether it exceeds the dynamic pressure the element is rated for.

Which pressure type should a 1.6 MPa loop use? That is the one rating where the table leaves it open: 1.6 MPa is offered as both gauge and sealed gauge. Gauge suits a vented cabinet where the reading is compared with a local gauge; sealed gauge suits a sealed enclosure, a cold surface, or anywhere a vent path could draw in condensation. Beyond that row the choice disappears, because every rating above it is sealed gauge.

Can the same unit be used on the primary and secondary loops? Only if both loops sit inside the same pressure envelope and the same coolant compatibility. Primary loops often run a different glycol concentration and a different inhibitor package, and the wetted material question has to be answered for each.

Can a pressure transmitter be used with glycol-based coolant? The medium name is not enough to answer it. Compatibility depends on the glycol concentration, the inhibitor formulation, the chloride level, the operating temperature and how long the loop sits idle, and it has to be settled for the wetted metal and the seal material separately. A grade that is correct for one inhibited glycol can be the wrong choice for another concentrate at the same temperature.

Why does surge protection matter in a CDU at all, when the working pressure is low? Because surge is a dynamic event, not a high-pressure one. Pump start and stop, a fast-closing valve, and pressure pulsation from the pump all produce peaks that sit above the steady reading while the loop is running at a modest pressure. Selection should weigh the peak amplitude, how often it happens, the dynamic pressure the transmitter is rated for, and whether a snubber or a pulsation damper belongs in front of the port.